API 650 aluminum storage tanks roof manufacturer
The materials used in the construction of Appendix Q oil tanks may be subject to severe pitting, cracking, or rusting if they are exposed to contaminated test water for extended periods of time. The Purchaser shall specify a minimum quality of test water that conforms to Q.8.3.2 through Q.8.3.8. After the water test is completed, the tank API 650 aluminum storage tanks shall be promptly drained, cleaned, and dried.
Design calculations and drawings required API 650 aluminum storage tanks for the fabrication and erection of each API 650 tank. A drawing index for each API 650 tank is required and shall be re-submitted each time drawings are revised and re-issued.
The cone slope of the completed API 650 aluminum storage tanks foundation is 15/1000 for the general foundation and less than 35/1000 for the soft foundation. After the foundation settlement of the storage tank is basically stable, the surface slope must be greater than eight thousandths. The edge of the tank bottom should be more than 0.3 meters higher than the surrounding ground. Above the ground, the tank bottom leakage detection tube should be drawn from the foundation sand cushion and cross the foundation ring wall or the slope protection surface. The circumferential distance should be less than 20 meters, and each API 650 aluminum storage tanks should have at least 4 detection tubes.