EN S355J0 plates API standard 650 low-alloy steel tanks
API standard 650 low-alloy steel tanks foam generator is a fire extinguishing device fixed on the oil tank. One end of the foam generator is connected to the foam pipeline, and one end is flanged on the top layer of the API standard 650 low-alloy steel tanks wall. Fire extinguishing foam flows through the air intake entrance of the fire foam chamber, inhaling a large amount of air to form foam, and breaking through the insulating glass into the tank (glass thickness is not greater than 2mm), so as to achieve the purpose of fire fighting.
In this project, a cylindrical tank 62 ft 6 in. in diameter is designed for an internal pressure of 4 lbf/in.2 gauge in the vapor space. The plate material is ASTM A131 steel with appropriate grades for different plate thicknesses in accordance with Table 4-1 for a design metal temperature less than 65°F but not less than 25°F. No corrosion allowance is required for any portion of the tank. The top course of the butt-welded cylindrical sidewall is 1/4 in. thick. The roof is a single lap-welded spherical dome with an internal radius of 50 ft and a thickness of 1/4 in. The maximum design liquid level is 6 in. below the plane of the juncture of the tank API standard 650 low-alloy steel tanks roof and sidewall.
For API 650 tanks Projection from outside of tank shell to extreme face of flange - plus or minus 5 mm. API standard 650 low-alloy steel tanks Elevation or radial location - plus or minus 6 mm. API 650 tanks Flange tilt in any plane, measured on the diameter across the gasket surface - plus or minus degree but not exceeding 5 mm. Flange bolt hole orientation - plus or minus 2 mm.