ASTM A181 forgings API standard 650 mechanically-anchored steel tanks

Before the start of erection, inspect each API 650 tank foundation to ensure that it is level and acceptable to receive Work. Remove temporary erection attachments welded to the interior or exterior of the API standard 650 mechanically-anchored steel tanks shell or to the bottom by arc gouging, and grind weld area smooth.

API standard 650 mechanically-anchored steel tanks, Oil tanks can be divided into above ground storage tanks, underground storage tanks, offshore tanks and submarine tanks according to their installation positions. Oil tanks can be divided into crude oil tanks, fuel oil tanks, lubricating oil tanks, edible oil tanks, etc.. According to the use of oil tanks, oil tanks can be divided into production tanks, storage tanks, etc.. According to the external style, oil tanks can be divided into vertical tanks, horizontal tanks, etc.. According to the composition structure, oil tanks can be divided into fixed roof storage tank, floating roof tank, spherical tank, etc.

"Hard and solid, honest commitment, practical effect". To strive for a solid enterprise foundation with hard work style; to promise first-class enterprise service with honest faith; to create efficient enterprise performance with practical spirit.

API standard 650 mechanically-anchored steel tanks Visual InspectionUpon completion of all the foregoing tests, the pressure in the tank shall be released and a thorough visual inspection shall be made of both the inside and outside of the tank, giving particular attention to all internal ties, braces, trusses, and their attachments to the walls of the tank. Anchors shall be checked for snug tightness and adjusted if required. Anchor threads shall be fouled by peening or tack welding to prevent loosening. In lieu of thread fouling, double nuts may be used.Rate of Water Filling and Water TemperatureThe rate at which water is introduced into a tank for a hydrostatic test shall not exceed 3 ft of depth per hour. The foundation, venting equipment, or other conditions may limit the water filling to a lower rate. Pressure shall not be applied above the surface of the water before the tank and its contents are at about the same temperature.

Have a question? Get a Free Consultation

If you are interested in our storage tanks, you can get contact with us through online consulting, demand table submission, e-mails and telephones.

Corporate Office

High-Tech Development Zone, Zhengzhou, China

Contact us

+86-371-86151527
[email protected]

Send a Message!